When was pool bonding first required by code?

Sunday, May 5, 2019

Stray electrical currents, or differences in electrical potential between two points, can occur between a pool, the pool equipment, and the surrounding metal objects such as nearby windows of a home. So the National Electrical Code (NEC) requires that the pool equipment, and all metal within a 5-foot radius of the edge of the pool up to 12-feet high be connected together with copper wiring to the metal reinforcing steel in the pool and the panel ground. This is called equipotential bonding.

    Swimming pools first appeared in the NEC in the 1962 edition, and the section was a brief three pages long. Here’s the first bonding citation in the 1962 code, although it was not initially called bonding:

680-7. Grounding
- (a) All metallic conduit, piping systems, pool reinforcing steel, light fixtures, and the like, shall be bonded together and grounded to a common ground. The metal parts of ladders, diving boards, and their support, shall be grounded.
- (b) No pool equipment shall be grounded to an external grounding electrode that is not common to the pool ground (deck box or transformer enclosure).
- (c) An unbroken No. 14 AWG, or larger, insulated copper wire shall be provided for a grounding conductor from the deck box to the distribution panel ground.
- (d) Metallic raceways shall not be depended upon for grounding. Where exposed to pool water and in other corrosive areas such as in pump houses or adjacent to water treating and other equipment, the grounding of the non-current carrying parts shall be by means of an insulated copper conductor sized in accordance with Section 250-95.

    The 1965 edition changed the ground wire requirement from #14 AWG to the larger #8 AWG, along with other minor additions. Then the 1968 edition introduced the word “bonding” for the unbroken connection between all components that was required, and specified the five-foot radius rule that we know today. Equipotential bonding code has continued to be improved in each code cycle up to today. 

    While the year that the NEC added a new requirement is easy to define, each local juridiction’s building codes don’t necessarily adopt the latest edition of the NEC immediately. The state of Florida, for example, did not make the 2011 NEC effective until mid-2015. Other jurisdictions have sometimes waited even longer to adopt a newer NEC edition and, to complicate things further, they might make amendments that exclude parts of the newest requirements. So the year when the NEC first adds or changes a requirement can be several years before your local building department adopted that edition of the code and began enforcing it.

    Also, see our blog post What are the clearance requirements for an overhead electric service drop that is directly over or near a swimming pool?


• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Here’s links to a collection of our other blog posts about POOL AND SPA:

• Why is my pool ladder rusting? 

Does an above-ground pool require a building permit? 

Does an above-ground pool have to comply with code requirements for a swimming pool barrier?

What are the pros and cons of vinyl liner vs fiberglas vs concrete in-ground pools? 

Can a pool with green, cloudy water be inspected?

Should I refinish-resurface my pool with paint or plaster?

Why are pool pumps now required to be variable speed? 

• Is the deteriorated finish of a concrete pool shell only a cosmetic problem? 

   Visit our POOL AND SPA page for other related blog posts on this subject, or go to the INDEX for a complete listing of all our articles.

Thanks to Jerry Peck, Construction/Litigation Consultant, for his code history notes used for this article.

Water Heaters

Water Heater Age

"What Are The

Signs Of..."

Septic Tank Systems

Structure and Rooms

Plumbing Pipes

Termites, Wood Rot

& Pests

Sinkholes

Stairs

When It First

Became Code

"Should I Buy A..."

Park Model Homes

Site

Shingle Roofs

Safety

Stucco

Remodeling

Wind Mitigation

Roof and Attic

"Does A Home

Inspector...?"

Pool and Spa

"What Is The Difference Between..."

Radon

Brick

Plumbing

Concrete and

Concrete Block

Metal Roofs

Foundations

Modular Homes

Rain Gutters

Mold, Lead & Other Contaminants

Condominiums

Older and

Historic Houses

Crawl Spaces

Mobile-Manufactured Homes

Building Permits

Life Expectancy

Clay Soil

Insurance

Floors

Insulation

Toilets

Exterior Walls

& Structures

Generators

Common Problems

HUD-Code for

Mobile Homes

Garages and Carports

Flat (Low Slope) Roofs

Electrical Panels

Sprinkler Systems

Electrical Receptacle Outlets

4-Point Inspections

Hurricane Resistance

Frequently Asked Questions (FAQ)

Home Inspection

Heating and Air Conditioning

Building Codes

Fireplaces and Chimneys

Inspector Licensing

& Standards

Energy Efficiency

Washers and Dryers

Electrical

Kitchens

Doors and Windows

(placeholder)

Cracks

Electrical Wiring

Click Below  

for Links

to Collections

of Blog Posts

by Subject

Plumbing Drains

and Traps

Appliances

Smoke & CO Alarms

Aging in Place

Top 5 results given instantly.

Click on magnifying glass

for all search results.

Bathrooms

Lighting

AFCI, CAFCI,

DFCI, & GFCI

Sinks

Air Conditioner & Furnace Age/Size

Attics

Electrical Switches

Siding

Search

This

Site

Water Intrusion

Electrical - Old

and Obsolete

(placeholder)

Foundation Certifications

Tiny Houses

About McGarry and Madsen

(placeholder)

Wells

Buying a home in North/Central Florida? Check our price for a  team inspection by two FL-licensed contractors and inspectors. Over 8,500 inspections completed in 20+ years. In a hurry? We will get it done for you.

Moisture Problems

Crawl Spaces

Bedrooms

Closets